High Voltage Digital Insulation Tester MS5215
Model Number: MS5215
Key Specifications / Features
♦Checking the insulation of high-voltage electrical equipment (electric motor, transformer, and cable, etc)
♦Test Voltage from 250V to 5000V.
♦Insulation resistance up to 5TΩ
♦Short Current up to 3mA.
♦Auto Calculate PI (Polarization Index) and DAR (Dielectric absorption ratio).
♦Step-Voltage Measurement
♦Temperature measurement
♦Temperature compensation for insulation Test
♦Leakage Current measurement.
♦Data Storage function and uploading to PC by USB2.0 Interface.
♦Timer Function
♦Power Supply: LR6 Battery * 6 / rechargeable battery NI/ Charger: Input Voltage 100V to 240V,
♦Frequency 50Hz to 60 Hz, output voltage 12V DC 3A
♦Weight 2.5kg (not including Battery)
♦Size 284mm(L) * 230mm(W) * 125(H)
♦Test Voltage from 250V to 5000V.
♦Insulation resistance up to 5TΩ
♦Short Current up to 3mA.
♦Auto Calculate PI (Polarization Index) and DAR (Dielectric absorption ratio).
♦Step-Voltage Measurement
♦Temperature measurement
♦Temperature compensation for insulation Test
♦Leakage Current measurement.
♦Data Storage function and uploading to PC by USB2.0 Interface.
♦Timer Function
♦Power Supply: LR6 Battery * 6 / rechargeable battery NI/ Charger: Input Voltage 100V to 240V,
♦Frequency 50Hz to 60 Hz, output voltage 12V DC 3A
♦Weight 2.5kg (not including Battery)
♦Size 284mm(L) * 230mm(W) * 125(H)
Detail Information
Temperature compensation
For obtaining the insulation resistance under a temperature other than current ambient temperature.
Converts the measured value of resistance to the insulation resistance under a reference ,temperature,.and display the result.
Depending on the different properties of test objects, there are 10 modes of compensation.
♦Test Voltage Range DC250V to DC5KV
♦Voltage Set:
Wide adjust: 250V, 500V, 1000V, 2.5kV, 5kV
Fine adjust: 250V to 1kV, step 25V, 1kV to 5kV, step 100V
♦Accuracy: 5%
♦Step mode: 500V, 1.0kV, 1.5kV, 2.0kV, 2.5kV
♦Test Current 1nA to 3mA
For obtaining the insulation resistance under a temperature other than current ambient temperature.
Converts the measured value of resistance to the insulation resistance under a reference ,temperature,.and display the result.
Depending on the different properties of test objects, there are 10 modes of compensation.
♦Test Voltage Range DC250V to DC5KV
♦Voltage Set:
Wide adjust: 250V, 500V, 1000V, 2.5kV, 5kV
Fine adjust: 250V to 1kV, step 25V, 1kV to 5kV, step 100V
♦Accuracy: 5%
♦Step mode: 500V, 1.0kV, 1.5kV, 2.0kV, 2.5kV
♦Test Current 1nA to 3mA
| Specification | ||
| Set test voltage | Test range | Accuracy |
| 250 V DC | 0.01MΩ~ 2.5GΩ | ±(5%rdg+5dgt) |
| 2.51GΩ~ 250GΩ | ±(20%rdg+10dgt) | |
| 500 V DC | 0.01MΩ~ 5.0GΩ | ±(5%rdg+5dgt) |
| 5.01MΩ~ 500GΩ | ±(20%rdg+10dgt) | |
| 1000V DC | 0.01MΩ~ 10GΩ | ±(5%rdg+5dgt) |
| 10.1GΩ~ 500GΩ | ±(20%rdg+10dgt) | |
| 501GMΩ~ 999GΩ | ±(20%rdg+20dgt) | |
| 2.5 KV DC | 0.01MΩ~ 25GΩ | ±(5%rdg+5dgt) |
| 25.1GΩ~ 500GΩ | ±(20%rdg+10dgt) | |
| 501GΩ~ 999GΩ | ±(20%rdg+20dgt) | |
| 1TΩ~ 2.5TΩ | ||
| 5KV DC | 0.01MΩ~ 50GΩ | ±(5%rdg+5dgt) |
| 50.1GΩ~ 500GΩ | ±(20%rdg+10dgt) | |
| 501GΩ~ 999GΩ | ±(20%rdg+20dgt) | |
| 1TΩ~ 5TΩ | ||
| Leak Current | ||
| Range | Measuring range | Accuracy |
| 10nA | 1.00nA ~ 9.99nA | ±(15%rdg+1nA) |
| 100nA | 9.0nA ~ 99.9nA | ±(15%rdg+5dgt) |
| 1000nA | 100nA ~ 999nA |
±(2.5%rdg+5dgt) |
| 10uA | 0.90uA ~ 9.99uA | |
| 100uA | 9.0uA ~ 99.9uA | |
| 1000uA | 90uA ~ 999uA | |
| 3mA | 0.90mA ~ 3.00mA | |
| Voltage Test | ||
| Test mode | DC voltage | AC voltage |
| Test range | ±(50V TO 1000V) | 50V TO 750V (50Hz to 60Hz) |
| Precision error | ±(5%rdg+5dgt) | |
| Input resistance | Approx 10MΩ | |
| Temperature test | ||
| Measuring range | Measuring precision | |
| -10℃to 0.1℃ | ±1.5℃ | |
| 0.0℃to 40.0℃ | ±1.0℃ | |
| 40.1℃to 70.0℃ | ±1.5℃ | |

Supplier Information
Mastech Meters & Testers Co., Ltd.
Verified Supplier
No. 879, Xiahe Road, Xiamen, Fujian, China
Est. 2005
Certifications:
ISO 9001
Comments